832AW-1A-C1 – RELAY (VDC)
Breaker off, disconnect pulled, then label every wire before you pull one. A fan relay has a normally closed set that is easy to mistake for the normally open set, and landing the blower on the wrong pair gives you a fan that runs when it should be off. Match coil voltage, contact arrangement and contact rating, not just the shape of the can. Bring the old relay in and we will bench test it free before you buy a new one.
10226 Plano Rd, Suite 104, Dallas TX 75238
Questions? Call or text (214) 340-9421
Mon–Fri 10 am – 7 pm | Sat 10 am – 3 pm
Song Chuan 832 series heavy duty general purpose power relay in the 832AW quick-terminal, flanged-cover configuration with a 1A single-pole normally open contact using AgSnO contact material. Song Chuan rates the 1A form at 30 A/240 VAC resistive with a 277 V maximum switching voltage. Coil voltage is set by the suffix appended to the base number and is not defined by 832AW-1A-C1 itself, so verify it on the relay.
Specifications published by the manufacturer. Source: manufacturer documentation.
Specs
- BrandSong Chuan
- TypeHeavy duty general purpose power relay
- Contact form1A - SPST-NO (AgSnO contact material)
- Contact rating30 A at 240 VAC resistive; 20 A at 30 VDC
- Max switching current / voltage30 A / 277 V
- Terminals & coverQuick terminal (W), flanged cover (C1)
- ApprovalsUL/cUL (UL 508 and 873), VDE
- Mechanical life10,000,000 operations
- Coil voltageSet by suffix - verify on the relay
Cross-reference numbers
This part replaces the following OEM and aftermarket numbers:
- 832AW-1A-C124VDC
- S1-02425986000
Not sure if your number matches? Call (214) 340-9421 or bring the old part in — bench-testing is free.
What is the difference between a fan relay and a contactor?
Duty and scale. A fan relay switches a blower or an accessory at a few amps off a 24 volt pilot duty coil. A contactor switches a compressor and condenser fan and is built for that inrush and arcing. A relay is not a small contactor. Use one as a contactor and it will pit and weld shut.
How do I pick the right replacement relay?
Match four things: coil voltage, contact arrangement, contact rating and the mounting. A White-Rodgers 90-370 is a Type 184 SPDT with a 24 VAC coil around 77 ohms DC resistance. A 90-340 is a Type 91 DPDT with a 24 VAC coil around 175 ohms. They look alike and are not interchangeable. SPDT gives you one normally open and one normally closed set, DPDT gives you two of each.
How do I test one?
Ohm the coil first, because an open coil is a dead relay. Then energize the coil with 24 volts, listen for the pull-in, and ohm the normally open contacts closed and the normally closed contacts open. A relay that clicks but will not pass current has burnt contacts, and that reads as a dead blower even though the control board is fine.
Why did the relay burn up?
Usually the load, not the relay. A blower drawing high amps because the run capacitor is weak or the wheel is caked with dirt pits relay contacts quickly. Fix the load or you will be back for another relay before the season ends.