S1-024-42184-000 – DOUBLE SHAFT BLOWER MOTOR (1 HP, 115V, 1100 RPM, YORK)
Double-shaft direct-drive blowers fail almost always because the cap got weak and the bearings overheated. Before driving over, pull the cap and bring it — we test free. If it's the motor, match HP, RPM, voltage, AND rotation direction (CW or CCW from shaft end). Wrong rotation will burn a new motor in days. Bring the old one in; we'll match it.
10226 Plano Rd, Suite 104, Dallas TX 75238
Questions? Call or text (214) 340-9421
Mon–Fri 10 am – 7 pm | Sat 10 am – 3 pm
If your indoor unit runs but produces weak or no airflow, the blower motor may need replacement. This is a York OEM double-shaft blower motor for specific York furnaces and air handlers. If your York unit’s blower has stopped, runs slowly, or makes noise, this is the factory replacement.
Specs: 1 HP, 115V, 1100 RPM, 4-speed, double shaft
Replaces: S1-024-42184-000, S1-02442184000, F48E34A48, F48T29A50, S83-536
Fits: York furnaces and air handlers. Bring your equipment model number and we’ll confirm the fit at the counter.
Need help? See our AC Not Cooling Troubleshooting Guide.
In stock at Open To Public HVAC Parts in Dallas. We test parts at the counter before you buy. Call or text (214) 340-9421.
Specs
- TypePSC double-shaft direct-drive blower motor
- Horsepower1 HP
- Voltage115V
- RPM1100 RPM
Cross-reference numbers
This part replaces the following OEM and aftermarket numbers:
- S1-024-42184-000
Not sure if your number matches? Call (214) 340-9421 or bring the old part in — bench-testing is free.
Fits these models
- Universal aftermarket replacement for older PSC direct-drive double-shaft blower motors
- Common applications: pre-2010 Rheem / Ruud / Goodman / Carrier / Bryant / Trane direct-drive blower assemblies
- Verify HP, RPM, voltage, AND rotation direction (CW or CCW viewed from shaft end) match your existing motor
How do I check rotation direction?
Look at the shaft end. CW (clockwise) viewed from the shaft means the blower wheel pulls air toward the motor body. CCW pulls air away. Wrong rotation will burn out the motor and break the wheel within days. The data plate marks rotation; bring the old motor in if it's faded.
What's 4-speed PSC mean?
The motor has 4 winding taps for different speeds, color-coded leads (typically black=high, blue=med-high, yellow=med-low, red=low, white=common). Wire to the speed tap your blower needs; cap unused leads.
Why do double-shaft motors keep failing?
Texas heat, weak run caps, and dirty squirrel-cage blowers cause 95% of double-shaft failures. Clean the blower wheel, replace the cap on schedule (every 5-7 years), and the motor will last.
Can I swap a 3-speed for a 4-speed?